5.4 MODULE 4 - S ETPOINT O UTPUT P ARAMETERS ( 4-SPt )
PARAMETER MENU
4-SPt
SEL
Backlight
Unit Only
Pro
SPSEL
Setpoint
Select
Act-n
Setpoint
Action
SPt-n
Setpoint
Value
HYS-n
Hysteresis
Value
tON-n
On Time
Delay
tOF-n
Off Time
Delay
rSt-n
Output Reset
Action
rEn-n
Output Reset
With Display
Reset Enable
Stb-n
Standby
Operation
brn-n
Probe
Burn-out
ChC-n
Change Display
Color with
Output State
SPSEL ?
?
Enb-2 ?
HYS-n ?
to
The Setpoint Output Parameters are only active when an optional output
module is installed in the meter.
SETPOINT SELECT
NO SP-1 SP-2
? NO
Enter the setpoint (output) to be programmed. The n in the following
parameters will reflect the chosen setpoint number. After the chosen setpoint
is completely programmed, the display will return to SPSEL . Repeat steps for
each setpoint to be programmed. Select NO to exit the module. The number of
setpoints available is setpoint output card dependent.
SETPOINT 2 ENABLE
YES NO
? NO
Select YES to enable Setpoint 2 and access the setup parameters. If NO is
selected, the unit returns to SPSEL and setpoint 2 is disabled.
SETPOINT ACTION
Act-n ? HI-bL           LO-bL           HI-Ub            LO-Ub
? HI-Ub
Enter the action for the selected setpoint (output). See Setpoint Output
Figures for a visual detail of each action.
SETPOINT VALUE
SPt-n ?
-9999 to 99999
100
Enter the desired setpoint value. The decimal point position for the setpoint
and hysteresis values follow the selection set in Module 1.
HYSTERESIS VALUE
1 59999
? 2
Enter desired hysteresis value. See Setpoint Output Figures for visual
explanation of how setpoint output actions (balanced and unbalanced) are
affected by the hysteresis. When the setpoint is a control output, usually
balanced hysteresis is used. For alarm applications, usually unbalanced
hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on
the low side for high acting setpoints and functions on the high side for low
acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay
can be used to prevent false triggering during process transient events.
ON TIME DELAY
tON-n ? 0.0 to 599.9 seconds
? 0.0
Enter the time value in seconds that the output is delayed from turning on
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
HI-bL
=
High Acting, with balanced hysteresis
OFF TIME DELAY
LO-bL
HI-Ub
LO-Ub
=
=
=
Low Acting, with balanced hysteresis
High Acting, with unbalanced hysteresis
Low Acting, with unbalanced hysteresis
tOF-n
?
?
0.0
0.0
to
599.9 seconds
SP + ?Hys
SP + ?Hys
Enter the time value in seconds that the output is delayed from turning off
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
SP
SP - ?Hys
Hys
SP
SP - ?Hys
Hys
ON
OUTPUT
ON
OUTPUT
OFF
STATE
TRIGGER POINTS
High Acting (Balanced Hys) =
OFF
HI-bL
OFF
STATE
TRIGGER POINTS
Low Acting (Balanced Hys) =
OFF
LO-bL
rSt-n
?
?
Auto
OUTPUT RESET ACTION
Auto LAtCH L-dLY
Enter the reset action of the output. See figure for details.
SP - Hys
SP
Hys
SP + Hys
SP
Hys
Auto = Automatic action; This action allows the output to automatically reset off
at the trigger points per the Setpoint Action shown in Setpoint Output
Figures. The “on” output may be manually reset (off) immediately by the
front panel RST button or user input.The output remains off until the trigger
point is crossed again.
ON
OUTPUT
High Acting (Unbalanced Hys) =
OUTPUT
ON
Low Acting (Unbalanced Hys) =
STATE
TRIGGER POINTS
OFF OFF
HI-Ub
STATE
OFF OFF
TRIGGER POINTS
LO-Ub
10
LAtCH = Latch with immediate reset action; This action latches the output on at
the trigger point per the Setpoint Action shown in Setpoint Output Figures.
Latch means that the output can only be turned off by the front panel RST
button or user input manual reset, serial reset command or meter power cycle.
相关PDF资料
CUB5USB0 USB OPTION CARD
CUB5VR00 METER LCD DC VOLT 8DIGIT
CUR-3285-MB BOX ABS 8.25X5.15X3.13" BLACK
CUR-3286-MB BOX ABS 10.15X6.15X3.13" BLACK
CUR-793-MB BOX ABS 4.1" X 2.23" X 2" W/BKTS
CUSTOM BGA CUSTOM BGA SOCKETS
CW2500 EPOXY OVERCOAT 0.26OZ
CW7000 BA DISPENSING PENS 2 PER PACKAGE
相关代理商/技术参数
CUB5TCR0 功能描述:THERMO METER REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5TR00 制造商:Red Lion Controls 功能描述:PRESET TIMR & CYCLE COUNTR W/REFL DSPLY 制造商:Red Lion Controls 功能描述:TIMER, ELECTRONIC , 8DIGIT, 9V TO 28V; Supply Voltage Range:9V DC to 28V DC; Panel Cutout Height:39.1mm; Panel Cutout Width:74.9mm; Time Range:- ;RoHS Compliant: Yes
CUB5USB0 功能描述:USB OPTION CARD RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5VB00 功能描述:DC VOLTMETER RED/GREEN BKLT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5VR00 功能描述:METER LCD DC VOLT 8DIGIT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB70000 功能描述:COUNTER 8-DIGIT REFLECTIVE DISP RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB70010 功能描述:COUNTER 8-DIGIT YEL/GRN BACKLIT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB70020 功能描述:COUNTER 8-DIGIT RED BACKLIGHT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:CUB7 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮